Overview of Microgrid Results

Microgrid Name Generation Bus Minimum 1 hr Load (kW) Average 1 hr Load (kW) Average Daytime 1 hr Load (kW) Maximum 1 hr Load (kW) Minimum 1 hr Critical Load (kW) Average 1 hr Critical Load (kW) Average Daytime 1 hr Critical Load (kW) Maximum 1 hr Critical Load (kW) Existing Fossil Generation (kW) New Fossil Generation (kW) Existing Solar (kW) New Solar (kW) Existing Battery Power (kW) Existing Battery Energy Storage (kWh) New Battery Power (kW) New Battery Energy Storage (kWh) Existing Wind (kW) New Wind (kW) Total Generation on Microgrid (kW) Renewable Generation (% of Annual kWh) Emissions (Yr 1 Tons CO2) Emissions Reduction (Yr 1 % CO2) Average Outage Survived (h) O+M Costs (Yr 1 $ before tax) CapEx ($) CapEx after Tax Incentives ($) Net Present Value ($)
mg0 634 789 1,493 1,913 2,713 60 178 248 306 0 306 440 1,223 79 307 58 0 0 0 2,107 17 5,461 13 8,760 42,523 2,538,441 1,624,482 881,452
mg1 675 789 1,493 1,913 2,713 211 403 498 713 0 713 800 2,852 0 0 258 480 0 0 4,623 37 4,359 27 8,760 108,230 6,024,948 3,915,518 1,399,574
mg2 684 789 1,493 1,913 2,713 317 551 684 909 81 909 0 3,637 20 100 161 179 0 0 4,808 37 4,669 29 8,760 135,362 7,189,760 4,560,440 2,162,349
mg3 646 789 1,493 1,913 2,713 25 139 216 385 0 385 0 1,538 0 0 144 214 0 0 2,068 16 5,563 15 8,760 44,378 3,307,803 2,173,351 1,064,959
Summary None 789 1,493 1,913 2,713 613 1,271 1,646 2,313 81 2,313 1,240 9,250 99 407 621 873 0 0 13,606 27 20,052 21 8,760 330,493 19,060,952 12,273,791 5,508,334

Report Generated

2024-07-30 13:28:32.547963

User Warnings

Pre-existing battery battery_634_existing will not be utilized to support loads in microgrid mg0.
Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system.
Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.
Pre-existing battery battery_684_existing will not be utilized to support loads in microgrid mg2.

Distribution Upgrades needed to create Microgrids

Microgrid Location Recommended Upgrade Component Count Cost Estimate ($)
mg0 mg0 Microgrid Design 1 100,000
mg0 mg0 Microgrid Controls 1 100,000
mg0 632633 SCADA disconnect switch 1 50,000
mg0 634a_data_center AMI disconnect meter(s) 1 300
mg0 634b_radar AMI disconnect meter(s) 1 300
mg0 634c_atc_tower AMI disconnect meter(s) 1 300
mg1 mg1 Microgrid Design 1 100,000
mg1 mg1 Microgrid Controls 1 100,000
mg1 671692 SCADA disconnect switch 1 50,000
mg1 675a_hospital 3-phase relay(s) 1 20,000
mg1 675b_residential1 3-phase relay(s) 1 20,000
mg1 675c_residential1 3-phase relay(s) 1 20,000
mg1 692_warehouse2 3-phase relay(s) 1 20,000
mg2 mg2 Microgrid Design 1 100,000
mg2 mg2 Microgrid Controls 1 100,000
mg2 671684 SCADA disconnect switch 1 50,000
mg2 684_command_center AMI disconnect meter(s) 1 300
mg2 652_residential AMI disconnect meter(s) 1 300
mg2 611_runway AMI disconnect meter(s) 1 300
mg3 mg3 Microgrid Design 1 100,000
mg3 mg3 Microgrid Controls 1 100,000
mg3 632645 SCADA disconnect switch 1 50,000
mg3 645_hangar AMI disconnect meter(s) 1 300
mg3 646_office AMI disconnect meter(s) 1 300

Description